Title of article
Accurate modelling of rod driven tower footing
Author/Authors
Almeida، نويسنده , , M.E.، نويسنده , , Correia De Barros، نويسنده , , M.T.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
4
From page
1606
To page
1609
Abstract
For evaluating the lightning performance of
transmission lines by computer simulation, the accurate
modelling of tower footing is very important. In particular, the
decrease of the earth resistance observed for high values of the
current flowing from the tower to earth has to be considered.
In this paper, different modelling approaches allowing to take
into accouut the non-linear behaviour of the tower footing are
overviewed, and a uew model to describe the soil ionization
process is presented. The proposed model corresponds to
considering the ionized soil region as an equifield shell. In
order to represent the ionization phenomena, the values of the
resistivity on the ionized region are decreased according to the
local current density, and the electric field is kept at a critical
value. Deionization of the soil is also taken into account.
Simulation results are presented, and compared to the
published results of experimental tests.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1996
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399229
Link To Document