• Title of article

    Performance of reduced wall EPR insulated medium voltage power cables. II. Mechanical characteristics

  • Author/Authors

    Yingli Wen  Cinquemani، نويسنده , , P.L. ، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    6
  • From page
    579
  • To page
    584
  • Abstract
    For the replacement of paper insulated lead covered cables (PILC) reduced insulation wall designs have been developed. They provide a reliable lower diameter cable design for installation in existing PILC conduits. Representing Part II of the investigation, this paper presents the results of mechanical testing conducted on both reduced and full wall EPR insulated cables. Both jacketed and non-jacketed cable designs have been subjected to mechanical pulling forces which greatly exceed recommended industry limitations, followed by electrical testing to ascertain cable performance. The results of this study conclude that reduced wall EPR insulated cables can safely withstand the same pulling forces as recommended for conventional walls and can be designed for installation under the same pulling limitations.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1997
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number