Title of article
Controlled closing on shunt reactor compensated transmission lines. II. Application of closing control device for high-speed autoreclosing on BC Hydro 500 kV transmission line
Author/Authors
Froehlich، نويسنده , , K. Hoelzl، نويسنده , , C. Stanek، نويسنده , , M. Carvalho، نويسنده , , A.C. Hofbauer، نويسنده , , W. Hoegg، نويسنده , , P. Avent، نويسنده , , B.L. Peelo، نويسنده , , D.F. Sawada، نويسنده , , J.H. ، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
6
From page
741
To page
746
Abstract
In the past, BC Hydro used circuit breaker closing
resistors to limit switching surges on its 500 kV transmission
system. This approach was considered undesirable for new
transmission lines and an innovative scheme incorporating
special transmission line surge arresters and controlled high
speed autoreclosing of the circuit breaker was developed. The
scheme and its basis as applied on a new 330 km long 500 kV
transmission line are described. Actual line switching tests,
also described, confirmed the validity of the studies performed
and applied design concepts, and the value of the scheme.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1997
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399384
Link To Document