Abstract
Because ofthe high MVA ratings, it would be expensive
to provide independent, equal, regulated dc voltage sources to
power the multilevel converters which are presently proposed for
STATCOMs. Dc voltage sources can be derived &om the dc link
capacitances which are charged by the rectified ac power. This
paper addresses two control issues: (1) regulation of the dc
capacitance voltages and (2) their equalization. Equalization is
necessary (i) to ensure the even sharing of voltage stresses in the
gate-turn-off thyristors (GTOs), and (ii) to prevent the
degradation of total harmonic distortion (THD) factors, as all
harmonic elimination strategies depend on qual voltages in their
assumptions. The strategies considered are: (a) the Fundamental
Frequency Method, @) the Sinusoidal Pulse Width Modulation
Method. Digital Simulations are used to confirm the Feasibility of
the control methods.