Title of article
Relation of insulation resistance and deteriorated ratio of reference voltage of oil-immersed surge arrester elements enclosed in pole transformers
Author/Authors
Uchida، نويسنده , , S.، نويسنده , , Mochizuki، نويسنده , , K.، نويسنده , , Araki، نويسنده , , K.، نويسنده , , Kaku، نويسنده , , I.، نويسنده , , Sakuraba، نويسنده , , Y.، نويسنده , , Takeshina، نويسنده , , T.، نويسنده , , Shirakawa، نويسنده , , S.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
6
From page
453
To page
458
Abstract
About. t,en years have passed since oil immersed
surge arrester elements enclosed in 6.GkV pole transformers been
used. At, present, technical developments are being demanded t,o
judge t,he soundness of these oil immersed surge arrester element,s
by a simple method and easily judge whet.her t,hese elements can he
usecl or not. on site The authors empirically investigat,ed correlation
bet,ween t.he insulation resist,ance and the rleteriorat,ecl ratio of t,he
reference volt,age of t.hese oil-immersed surge arrester elements. It
was found that t,he det,eriorat,ion of the oil-immersed surge arrester
elements can be det,ectecl by measuring t,he insulation resistance by
a megger.
Keywords
distribution line , Oil-Immersed Transformer , Zinc Oxide Element , surge arrester , lightning