• Title of article

    Relation of insulation resistance and deteriorated ratio of reference voltage of oil-immersed surge arrester elements enclosed in pole transformers

  • Author/Authors

    Uchida، نويسنده , , S.، نويسنده , , Mochizuki، نويسنده , , K.، نويسنده , , Araki، نويسنده , , K.، نويسنده , , Kaku، نويسنده , , I.، نويسنده , , Sakuraba، نويسنده , , Y.، نويسنده , , Takeshina، نويسنده , , T.، نويسنده , , Shirakawa، نويسنده , , S.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    6
  • From page
    453
  • To page
    458
  • Abstract
    About. t,en years have passed since oil immersed surge arrester elements enclosed in 6.GkV pole transformers been used. At, present, technical developments are being demanded t,o judge t,he soundness of these oil immersed surge arrester element,s by a simple method and easily judge whet.her t,hese elements can he usecl or not. on site The authors empirically investigat,ed correlation bet,ween t.he insulation resist,ance and the rleteriorat,ecl ratio of t,he reference volt,age of t.hese oil-immersed surge arrester elements. It was found that t,he det,eriorat,ion of the oil-immersed surge arrester elements can be det,ectecl by measuring t,he insulation resistance by a megger.
  • Keywords
    distribution line , Oil-Immersed Transformer , Zinc Oxide Element , surge arrester , lightning
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1998
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number