• Title of article

    An investigation of transient overvoltage generation when switching high voltage shunt reactors by SF6 circuit breaker

  • Author/Authors

    Ma، نويسنده , , Z.، نويسنده , , Bliss، نويسنده , , C.A.، نويسنده , , Penfold، نويسنده , , A.R.، نويسنده , , Harris، نويسنده , , A.F.W.، van der Steen, نويسنده , , Tennakoon، S. B. نويسنده , , S.B.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    8
  • From page
    472
  • To page
    479
  • Abstract
    The work reported in this paper can he grouped iinto three categories: empirical investigations, analytical studies and computer simulations. The studies have identified the causes of high transient overvoltages which are produced when switching high voltage shunt reactors. Laboratory and site testing hiave shown that multiple reignition is the most likely cause of the high overvoltages. Circuit analysis has been carried out to identify the conditions which lead to multiple reignitions. A computer model has been developed to allow the likelihood of multiple reignitions occurring to be assessed.
  • Keywords
    Shunt reactor switching , Circuit breaker , EMTP MODELS , Arc qodels. , Multiplereignitions
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1998
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number