Title of article
Distance protection and fault location utilizing only phase current phasors
Author/Authors
Djuric، نويسنده , , M.B.، نويسنده , , Radojevic، نويسنده , , Z.M.، نويسنده , , Terzija، نويسنده , , V.V.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
7
From page
1020
To page
1026
Abstract
Two numerical algorithms for fault location and
distance protection which use data from one end of
transmission line are presented. Both algorithms require only
current signals as input data. Voltage signals are unnecessary
for determining the unknown distance to the fault. The solution
for the most frequent phase to ground fault is presented. The
algorithms are relatively simple and easy to be implemented in
the on-line application. The algorithms allow for accurate
calculation of the fault location irrespective of the fault
resistance and load. To illustrate the features of the new
algorithms, steady-state and dynamic tcsts are presented.
Keywords
computer relaying , distance protection , fault location.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1998
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399645
Link To Document