    Radio frequency signal transmission on medium voltage power distribution lines

  • Author/Authors

    Bukhala، نويسنده , , Z.A.، نويسنده , , Glinkowski، نويسنده , , M.T.، نويسنده , , Nelson، نويسنده , , J.K.، نويسنده , , Forte، نويسنده , , V.J.، نويسنده , , Jr.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1999
  • Pages
    6
  • From page
    46
  • To page
    51
  • Abstract
    A series of tests measuring HF signal attenuation were perfonned on a de-energized 15-kV three-phase power distribution feeder. The feeder consisted of a U-shaped line measuring approximately 2O8m in length with varying line geometry around the circuit. RF signals in the range of 2 to 30 MHz were injected in one phase of the feeder and the propagated responses were measured at two locations along the feeder. Tests were conducted with and without shunt power equipment (distribution transformers, arresters and capacitors) connected to the feeder. The characteristic line impedance of different line geometries was calculated by analytical means and found to be consistent with experimental results. Attenuation and characteristic impedance were found to be relatively constant at frequencies between 15 and 30 MHz with minimal influence from line geometry and power equipment placement.
  • Keywords
    Distribution , high-frequency propagation. , feeder