• Title of article

    Cable crossings-derating considerations. II. Example of derivation of derating curves

  • Author/Authors

    Anders، نويسنده , , G.، نويسنده , , Brakelmann، نويسنده , , H.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1999
  • Pages
    6
  • From page
    715
  • To page
    720
  • Abstract
    Cables crossing other heat sources either perpendicularly or at oblique angles will experience a rise in conductor temperature which should result in ampacity derating. In the first part of the paper a mathematical model for calculation of derating factors was presented. In this paper, a practical numerical example is considered with a pipe-type cable crossing a 10 kV distribution circuit. The numerical analysis presented here confirms experimental findings reported in the literature that the cable crossing may elevate conductor temperature by as much as 2OOC.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1999
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399818