    Design and field testing of a source based protection relay for wind farms

  • Author/Authors

    Haslam، نويسنده , , S.J.، نويسنده , , Crossley، نويسنده , , P.A.، نويسنده , , Jenkins، نويسنده , , N.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1999
  • Pages
    6
  • From page
    818
  • To page
    823
  • Abstract
    The paper describes the design and field testing of a soufce based relay suitable for the protection of wind farms with fixed-speed induction generators. The relay provides short-circuit protection for the medium voltage (MV) power collection circuit and the MV and low voltage (LV) windings of each generator transformer. The use of the relay allows a reduction in the construction cost of a wind farm, since MV fuses are no longer required to protect the generator transformers. The paper discusses how the protection algorithm was designed based on the electrical behaviour of induction generators operating in a wind farm. The relay was evaluated at a wind farm in Wales and also in the laboratory using data from a wind farm simulator and a transient recorder. The latter, installed at the wind farm, recorded the voltage and current signals measured during local disturbances. The recorded or simulated data was subsequently replayed into a relay simulator which graphically describes the operating behaviour of the protection.
  • Keywords
    Source Based Protection , Wind Farms , field testing , Multi-Function Relay
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1999