Title of article
Fault location of two-parallel transmission line for nonearth fault using one-terminal data
Author/Authors
Zhang Qingchao، نويسنده , , Zhang Yao، نويسنده , , Song Wennan، نويسنده , , Yu Yixin، نويسنده , , Wang Zhigang، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1999
Pages
5
From page
863
To page
867
Abstract
An accurate fault-location algorithm for
two-parallel transmission line of direct ground neutral
system is presented. The algorithm employs the faulted
circuit and healthy circuit of two-parallel line as faultlocation
model, in which remote source impedance is
not involved. It effectively eliminates the effect of load
flow and fault resistance on the accuracy of fault
location. It embodies an accurate location by
measuring only one local end data and it is used in a
procedure that provides the automatic determination of
fault types and phases, rather than requires engineer to
specify them. Simulation results have shown the
effectiveness of the algorithm under the conditions of
non-earth fault (phase-to-phase fault and three-phase
fault with and without earth-connection).
Keywords
phase-to-phase fault , three-phase fault , two-parallel transmission line , Fault location
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1999
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399838
Link To Document