Title of article
Evaluation of transmission line arresters against winter lightning
Author/Authors
Wakai، نويسنده , , T.، نويسنده , , Itamoto، نويسنده , , N.، نويسنده , , Sakai، نويسنده , , T.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2000
Pages
7
From page
684
To page
690
Abstract
The authors have tested 154 kV-class transmission
line arresters by installing them on an instrumented tower of
a double-circuit test transmission line during winter seasons
since 1993. The tower is struck by natural and artificially-triggered
lightning several times during each winter season. The
conventional transmission line arrester designed against summer
lightning was effective against winter lightning. The authors
developed a new transmission line arrester of reduced rating,
and investigated its applicability against winter lightning based
on EMTP analysis, taking account of measured lightning current
waveforms in winter. Although omission of an earth wire is not
feasible on transmission towers having high footing resistance, the
new arrester of reduced rating is a reasonable option to realize a
line of high lightning performance.
Keywords
Transmission line arrester , winter lightning , EMTP.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2000
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400036