    Evaluation of transmission line arresters against winter lightning

  • Author/Authors

    Wakai، نويسنده , , T.، نويسنده , , Itamoto، نويسنده , , N.، نويسنده , , Sakai، نويسنده , , T.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2000
  • Pages
    7
  • From page
    684
  • To page
    690
  • Abstract
    The authors have tested 154 kV-class transmission line arresters by installing them on an instrumented tower of a double-circuit test transmission line during winter seasons since 1993. The tower is struck by natural and artificially-triggered lightning several times during each winter season. The conventional transmission line arrester designed against summer lightning was effective against winter lightning. The authors developed a new transmission line arrester of reduced rating, and investigated its applicability against winter lightning based on EMTP analysis, taking account of measured lightning current waveforms in winter. Although omission of an earth wire is not feasible on transmission towers having high footing resistance, the new arrester of reduced rating is a reasonable option to realize a line of high lightning performance.
  • Keywords
    Transmission line arrester , winter lightning , EMTP.