Title of article
Elimination of transformer inrush currents by controlled switching. I. Theoretical considerations
Author/Authors
Brunke، نويسنده , , J.H.، نويسنده , , Frohlich، نويسنده , , K.J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
5
From page
276
To page
280
Abstract
Transformer inrush currents are high-magnitude,
harmonic-rich currents generated when transformer cores are
driven into saturation during energization. These currents have
undesirable effects, including potential damage or loss-of-life
to the transformer, protective relay misoperation, and reduced
power quality on the system. Controlled transformer switching
can potentially eliminate these transients if residual core and core
flux transients are taken into account in the closing algorithm.
This paper explores the theoretical considerations of core flux
transients. Based on these studies algorithms were developed
which allow controlled energization of most transformers without
inrush current.
Keywords
transformer switching. , residualflux , Controlled switching , inrush current
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2001
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400191
Link To Document