Title of article
Comparing direct and synthetic tests for interruption of line-charging capacitive current
Author/Authors
Daigneault، نويسنده , , G.، نويسنده , , Philippe St-Jean، نويسنده , , G.، نويسنده , , Landry، نويسنده , , M.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
6
From page
409
To page
414
Abstract
Using a validated arc model, this paper analyzes current
distortion and voltage waveforms during both direct and synthetic
tests for interruption of line-charging capacitive current by
power circuit breakers. Although the voltage of the electric arc
drawn between breaker contacts may produce significant current
distortion, it is demonstrated that the most significant parameter
affecting the breaking capacity of power circuit breakers in capacitive-
current switching tests is the voltage jump appearing across
breaker contacts immediately after current interruption. It is essential
to correctly define the supply circuit impedances and the
associated voltage jump so as not to reduce or increase this test
severity unduly.
Keywords
Capacitive-current switching , synthetic testing , current distortion , voltage jump. , circuit-breaker