• Title of article

    Comparing direct and synthetic tests for interruption of line-charging capacitive current

  • Author/Authors

    Daigneault، نويسنده , , G.، نويسنده , , Philippe St-Jean، نويسنده , , G.، نويسنده , , Landry، نويسنده , , M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2001
  • Pages
    6
  • From page
    409
  • To page
    414
  • Abstract
    Using a validated arc model, this paper analyzes current distortion and voltage waveforms during both direct and synthetic tests for interruption of line-charging capacitive current by power circuit breakers. Although the voltage of the electric arc drawn between breaker contacts may produce significant current distortion, it is demonstrated that the most significant parameter affecting the breaking capacity of power circuit breakers in capacitive- current switching tests is the voltage jump appearing across breaker contacts immediately after current interruption. It is essential to correctly define the supply circuit impedances and the associated voltage jump so as not to reduce or increase this test severity unduly.
  • Keywords
    Capacitive-current switching , synthetic testing , current distortion , voltage jump. , circuit-breaker
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2001
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    400212