Abstract
Estimation of Very Fast Transient Overvoltage
(VFTO) has been carried out using EMTP for various switching
conditions in a 420 kV gas insulated substation. The variation
of VFTO peak along the GIS bus nodes for disconnector and
circuit breaker switching operations as well as the variation of
VFTO peak with different magnitudes of trapped charges have
been studied. The results indicate a distinct pattern of variation
of VFTO peak along the nodes of the GIS bus in the case of
disconnector switch operation as compared to that of circuit
breaker operation. It has also been noticed that the variation of
VFTO peak levels are not in direct proportion to the trapped
charge present on the HV bus.