Title of article
Influence of representation model and voltage harmonics on metal oxide surge arrester diagnostics
Author/Authors
Zhu، نويسنده , , H.، نويسنده , , Raghuveer، نويسنده , , M.R.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
5
From page
599
To page
603
Abstract
Test results have been presented to demonstrate
the hysteretic character of the volt–ampere relation of a Metal
Oxide Surge Arrester (MOSA). Using a compensation technique
described in the paper, it is shown that the use of single valued
average volt–ampere characteristics does not introduce large errors
in simulation studies. Results from computer simulation are
presented to demonstrate the considerable influence of harmonics
in the applied voltage on the magnitude of diagnostic indicators.
Keywords
Diagnostic indicators , hysteretic volt–ampere relation , voltage harmonics. , Metal oxide surge arrester