Title of article
A new PMU-based fault location algorithm for series compensated lines
Author/Authors
Chi-Shan Yu ، نويسنده , , Chih-Wen Liu ، نويسنده , , Sun-Li Yu، نويسنده , , Joe-Air Jiang، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
14
From page
33
To page
46
Abstract
This paper presents a new fault location algorithm
based on phasor measurement units (PMUs) for series compensated
lines. Traditionally, the voltage drop of series device is computed
by the device model in the fault locator of series compensated
lines, but using this approach errors are induced by the inaccuracy
of the series device model or the uncertainty operation
mode of the series device. The proposed algorithm does not utilize
the series device model and knowledge of the operation mode
of the series device to compute the voltage drop during the fault
period. Instead, the proposed algorithm uses two-step algorithm,
prelocation step and correction step, to calculate the voltage drop
and fault location. The proposed technique can be easily applied to
any series FACTS compensated line. EMTP generated data using a
30-km 34-kV transmission line has been used to test the accuracy
of the proposed algorithm. The tested cases include various fault
types, fault locations, fault resistances, fault inception angles, etc.
The study also considers the effect of various operation modes of
the compensated device during the fault period. Simulation results
indicate that the proposed algorithm can achieve up to 99.95% accuracy
for most tested cases.
Keywords
FACTS , Series compensation , synchronizedphasor measurement units.
Journal title