Title of article
Safety aspects of GSM systems on high-voltage towers: an experimental analysis
Author/Authors
and J. B. M. van Waes، نويسنده , , J.B.M.، نويسنده , , van Deursen، نويسنده , , A.P.J.، نويسنده , , van Riet، نويسنده , , M.J.M.، نويسنده , , Provoost، نويسنده , , F.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
5
From page
550
To page
554
Abstract
Low-voltage (LV) applications mounted on
high-voltage (HV) towers may pose a safety problem in the low
voltage network when a flashover occurs over the high-voltage
insulators. To study the effects experimentally, a 150-kV system
was made available. On a high voltage tower carrying a cellular
phone base station, one phase insulator was shorted to the tower.
A current of about 200 A was injected into that phase at a large
distance. We measured the current distribution and the relevant
voltages in the low voltage net. The experimental current data
agree with EMTP calculations. Appropriate measures to guarantee
safety for persons and electronic equipment are discussed.
Keywords
Grounding , overvoltage , electric shocks , electricalfaults , EMC , safety , global system for mobile communication (GSM) , Transmission lines. , Distribution networks