GIC occurrences and GIC test for 400 kV system transformer
Author/Authors
Lahtinen، نويسنده , , M.، نويسنده , , Elovaara، نويسنده , , J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
7
From page
555
To page
561
Abstract
The geomagnetic induced currents in transmission
network may saturate transformers and cause additional losses, a
high level of harmonics, and a lack of reactive power in the grid.
Also, malfunctioning of protection circuits is reported in this paper.
The field tests made for two 463 MVA system transformers show
that tested transformers may tolerate very high dc currents for
times typical to geomagnetic storms. The effects of the voltage control
and voltage quality in network are also considered, and results
of earlier Finnish GIC risk studies are reported.
Keywords
DC-current , Geomagnetic , immunity , transformer.