Abstract
The degradation of electrical insulation in transformers
is more often due to thermal stress. In this paper, authors
have attempted to work out a method of assessing the magnitude
of temperature and the hottest region in the body of a large
transformer with a reasonable degree of accuracy. A theoretical
model has been developed based on boundary value problem
of heat conduction in transformer winding using finite integral
transform techniques. The model requires, in addition to electrical
parameters of the transformer, information on the actual design
data. The authors believe that this model predicts HST with
precision and also indicates a possibility of online data acquisition.