• Title of article

    Site variation and prediction of power quality

  • Author/Authors

    Short، نويسنده , , T.A.، نويسنده , , Mansoor، نويسنده , , A.، نويسنده , , Gretchen Sunderman، نويسنده , , W.، نويسنده , , Sundaram، نويسنده , , A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    7
  • From page
    1369
  • To page
    1375
  • Abstract
    We use EPRI’s distribution power quality project data to characterize and predict voltage sags and momentary interruptions based on site characteristics. The quality of sites is widely dispersed. Rural sites have many more sags and momentary interruptions than suburban and urban sites. The strongest indicators of voltage sags are 1) circuit exposure, 2) lightning, and 3) a term with transformer impedance and number of feeders. We develop a linear model for predicting sags and another for predicting momentary interruptions based on site characteristics. We also compare transmission-level power quality to distribution power quality.
  • Keywords
    interruptions , Power distribution , voltage sags. , power quality
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number