Title of article
Long-distance 275-kV GIL monitoring system using fiber-optic technology
Author/Authors
Miyazaki، نويسنده , , A.، نويسنده , , Takinami، نويسنده , , N.، نويسنده , , Kobayashi، نويسنده , , S.، نويسنده , , Nishima، نويسنده , , H.، نويسنده , , Nakura، نويسنده , , Y.، نويسنده , , Komeda، نويسنده , , H.، نويسنده , , Nagano، نويسنده , , H.، نويسنده , , Higashi، نويسنده , , H.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2003
Pages
9
From page
1545
To page
1553
Abstract
This paper reports the monitoring system applied for
a long- distance 275-kV gas-insulated transmission line (GIL) [1]
using the latest fiber-optic technology. The monitoring system consists
of two major parts—one monitors the GIL itself, for example,
the insulated gas pressure and the surface temperature of the GIL
enclosure, fault localization, etc. The other monitors the conditions
of the tunnel, where the GIL is installed. To construct a more simple
and reliable system, we have developed and applied certain kinds
of optical sensors and measuring equipment This system was verified
to be effective through a loading test on an actual GIL and a
high voltage test, etc. and has been put into actual operation service
since February 1998.
Keywords
monitoring system. , Fault localization , fiber-optic gas density sensor , fiber-optic temperature distribution sensor , gas-insulated transmissionline