Title of article
Calculating the Transient Recovery Voltage Associated With Clearing Transformer Determined Faults by Means of Frequency Response Analysis
Author/Authors
M. Steurer، نويسنده , , W. Hribernik، نويسنده , , and J. H. Brunke، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
6
From page
168
To page
173
Abstract
The transient recovery voltage (TRV) associated
with power-transformer terminal faults is essential for correctly
applying circuit breakers. Because presently used methods only
allow for roughly estimating an equivalent single TRV ringing
frequency, more accurate but inexpensive methods are needed.
The novel method presented in this paper employs frequency
response analysis (FRA) for measuring the transformer’s complex
short circuit impedance . From that, the frequency spectrum
of the TRV is approximated by the ratio of over the frequency
square. Inverse fast Fourier transformation finally leads to the
time domain signal. Comparing measured TRV signals from
several field tests with the calculated ones prove this simple but
effective method. Even multimode oscillations that cannot be
reproduced by rough estimating tools are covered. It is concluded
that the presented method provides a valuable tool for extracting
inherent TRV parameters, either from routinely performed FRA
measurements or from lightning impulse tests without significant
additional costs.