Title of article
Power Flow Analysis on Simplified Feeder Modeling
Author/Authors
J. Liu، نويسنده , , B. Pengxiang، نويسنده , , Z. Yanqing، نويسنده , , and W. Xiaomeng، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
9
From page
279
To page
287
Abstract
Three novel models to simplify distribution network
analysis are presented including equivalent load model (ELM),
equivalent load density model (ELDM), and discrete equivalent
load density model (DELDM). The voltages and the power
on/through both ends of a feeder are used to describe the load and
its distribution pattern within the feeder line. Only real time field
data from feeder circuit breakers in substations and sectionalizing
switches along the feeder lines are needed to obtain a satisfied
analysis result. The loads on the feeder are represented by one
load in ELM. Six fundamental load distribution patterns are
put forward in ELDM. By solving the voltage drop function and
the power loss function of the feeder line, characteristic values
together with the corresponding similarity parameters for the six
load distribution patterns are obtained, respectively. Weighting
values for the six load distribution patterns are calculated, respectively.
Consequently, voltage drop and line loss can be acquired
without needing the data from each distribution transformer on
the feeder line. Based on above method, a discrete equivalent load
density model is advanced to improve the property. Examples are
also given with comparison with other approaches showing the
feasibility of the proposed methods.
Keywords
analysis , Distribution Automation , Feeder Automation , power flow calculation. , MODELING
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2004
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400589