An Islanding Detection Method for Distributed Generations Using Voltage Unbalance and Total Harmonic Distortion of Current
Author/Authors
S.-I. Jang and K.-H. Kim، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
8
From page
745
To page
752
Abstract
Distributed generation (DG) units are rapidly
increasing and most of them are interconnected with distribution
network to supply power into the network as well as local loads.
Islanding operations of DG usually occur when power supply
from the main utility is interrupted due to several reasons but the
DG keeps supplying power into the distribution networks. These
kinds of islanding conditions cause negative impacts on protection,
operation, and management of distribution systems; therefore, it is
necessary to effectively detect the islanding conditions and swiftly
disconnect DG from distribution network. Generally, if there are
large changes in loading for DG after loss of the main power
supply, then islanding conditions are easily detected by monitoring
several parameters: voltage magnitude, phase displacement, and
frequency change. However, in case of small changes in loading for
DG, the conventional methods have some difficulty in detecting
such a particular islanding condition. This paper presents a new
islanding detection algorithm for DG effectively working in the
most of DG loading conditions. This paper proposes two new
parameters for detecting islanding operation of DG: voltage
unbalance and total harmonic distortion of current. The proposed
method effectively combines the conventional parameters with the
newly proposed parameters for detecting the islanding conditions.
The proposed methods were verified using the radial distribution
network of IEEE 34 bus.
Keywords
Distributed generations (DGs) , islanding detection.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY