Abstract
This paper presents a numerical analysis of losses
generated in the tank-wall surrounding the high-current bushings
of pad-mounted transformers using a three-dimensional (3-D) finite-
element approach. Two cases are analyzed to study the impact
of inserting small plates of different geometry (located near
the high-current phases) on the reduction of tank losses. Significant
reductions in stray losses occurring in the tank wall are obtained
with plate inserts of low-cost.With the “T” configuration proposed
in this paper, we reduce the tank-wall losses by a factor of 1/21 at
rated current when compared with the case of tank wall without
the stainless-steel plate. A 3-D time-harmonic finite-element model
is used to determine the losses in the tank wall. Two load loss tests
were carried out on experimental transformers to validate the simulations
and effectiveness of the low-cost inserts.