• Title of article

    Melting and breaking characteristics of OPGW strands by lightning

  • Author/Authors

    Goda، نويسنده , , Y.  Yokoyama، نويسنده , , S.  Watanabe، نويسنده , , S.  Kawano، نويسنده , , T.  Kanda، نويسنده , , S. ، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    6
  • From page
    1734
  • To page
    1739
  • Abstract
    Some strands were melted and broken in a 140 mm2 OPGW (composite fiber-optic ground wire) in a 187 kV transmission line. It was assumed that this was caused by a lightning strike. DC arc tests simulating lightning strikes were carried out, and the melting and breaking characteristics of OPGW strands were obtained. The electric charge of the lightning strike that damaged the OPGW was estimated from the number of strands broken by the DCarc. In this paper, theDCarc test results, and the test conditions required to simulate a powerful lightning strike are described.
  • Keywords
    transmission lines. , Arc discharges , Lightning , optical fiber cables