Title of article
Envelope tracking techniques for FlickerMitigation and Voltage regulation
Author/Authors
Marei، نويسنده , , M.I. El-Saadany، نويسنده , , E.F. Salama، نويسنده , , M.M.A. ، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
8
From page
1854
To page
1861
Abstract
Envelope tracking has many important applications
in electrical distribution systems for either flicker meters or flicker
compensators. This paper presents a novel control technique for
flicker mitigation. This technique is based on the instantaneous
tracking of the measured voltage envelope. The ADAptive LINEar
neuron (ADALINE) algorithm, and the Recursive Least Square
(RLS) algorithm are introduced for the flicker envelope tracking.
The ADALINE algorithm is characterized by a light computational
demand, unlike that of existing techniques; the RLS
algorithm outperforms the ADALINE algorithm by its fast convergence
and robust tracking performance. Both the ADALINE
and the RLS algorithms give accurate results even under rapid
dynamic changes. The paper investigates the effects of different
parameters on the performance of the ADALINE algorithm and
that of the RLS algorithm. Extensive simulations of the proposed
flicker tracking algorithms are conducted to evaluate their performance
for the tracking and mitigation of voltage flicker. The
ADALINE and the RLS algorithms are examined by tracking
and mitigating the flicker produced by a resistance welder and
an arc furnace in a simple distribution system simulated in the
PSCAD/EMTDC package.
Keywords
flickermitigation , least mean square methods , power quality , recursiveestimation , voltage control. , envelope tracking , Adaptive estimation
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2004
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400805
Link To Document