Title of article
Development and hardware implementation of a compensating algorithm for the secondary current of current transformers
Author/Authors
Kang، نويسنده , , Y.C.; Kang، نويسنده , , S.H.; Park، نويسنده , , J.K.; Johns، نويسنده , , A.T.; Aggarwal، نويسنده , , R.K.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
9
From page
41
To page
49
Abstract
The conventional method of dealing
with current-transformer (CT) saturation is
overdimensioning of the core so that CTs can
reproduce up to 20 times the rated current
without exceeding 10% ratio correction. However,
this not only reduces the sensitivity of relays, as
some errors may still be present in the secondary
current when a severe fault occurs, but also
increases the CT size. An algorithm is described
for estimating the secondary current
corresponding to the CT ratio under CT
saturation using the fluxkurrent (hli) curve, and
the results of hardware implementation of the
algorithm using a digital signal processor are also
presented. The main advantage of the algorithm
is that it can improve the sensitivity of relays to
low-level internal faults, maximise the stability of
relays for external faults, and reduce the required
CT-core cross-section significantly.
Keywords
Saturation , Current transformers , Compensators
Journal title
IEE Proceedings Electric Power Applications
Serial Year
1996
Journal title
IEE Proceedings Electric Power Applications
Record number
402240