Title of article
DC magnetisation of transformers
Author/Authors
A.J.; Ahfock، نويسنده , , A.; Hewitt، نويسنده , , A.J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2006
Pages
7
From page
601
To page
607
Abstract
A sufficiently high DC component in the current on the secondary side of a transformer
causes distortion of the primary side current. Prediction of such distortion relies on the availability
of magnetisation curves that extend deep enough into saturation. A simple test, carried out at rated
voltage, is proposed which allows the magnetisation curve to be deduced from measured data. In
addition, a systematic procedure has been developed to evaluate the primary-current distortion in
both single- and three-phase transformers. Comparison between theoretical predictions and
practical measurements are made, with reasonable agreement between the two.