• Title of article

    Measurement and calculation of the neutral height in a room with displacement ventilation

  • Author/Authors

    Huijuan Xing، نويسنده , , Hazim B. Awbi، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    7
  • From page
    961
  • To page
    967
  • Abstract
    This paper investigates the relationship between the neutral height for air distribution and the ventilation load in a room with displacement ventilation. An environmental chamber equipped with a displacement ventilation system has been used to carry out the neutral height measurements with the presence of a heated mannequin and other heat sources in the chamber. The total room load used was varied from 104 to 502 W, i.e., corresponding to a ventilation load from 10 to 60 W/m2. The prediction of the neutral height was based on plume theory. Comparison between the experimental data and the predictions showed good agreement. The prediction also showed that human body could draw uncontaminated fresh air from the lower zone, which improves the air quality in breathing zone.
  • Keywords
    Displacement ventilation , Neutral height , Indoor Air Quality , Buoyancy plume
  • Journal title
    Building and Environment
  • Serial Year
    2002
  • Journal title
    Building and Environment
  • Record number

    408525