• Title of article

    Influence of plates on flow inside a recessed space generated by rejected heat

  • Author/Authors

    M. Bojic، نويسنده , , F. Yik، نويسنده , , M. Lee، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    12
  • From page
    593
  • To page
    604
  • Abstract
    In this paper, we report investigations into temperature and flow field inside a recessed space outside a high-rise residential building in Hong Kong. The investigated 30-story recessed spaces contain 30 air-conditioners, and one or two horizontal plates. We studied the worst-case scenario in summer when all air-conditioner units reject condenser heat into this space. The predictions by using FLUENT 5.0, a computational fluid dynamics code, show that presence of one plate inside the space would cause the overall excess temperature at condenser entrance to fall up to 30%. The presence of two plates would make this figure to be around 40%.
  • Keywords
    Air-conditioners , Heat rejection , High-rise residential buildings , Recessed spaces , Temperature rise
  • Journal title
    Building and Environment
  • Serial Year
    2003
  • Journal title
    Building and Environment
  • Record number