Title of article
On the control of heating systems in the UK
Author/Authors
Z. Liao ، نويسنده , , M. Swainson، نويسنده , , A.L. Dexter، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
9
From page
341
To page
349
Abstract
This paper reviews current heating system control practice in the UK through surveys, computer simulation and experimental
studies. It is evident from the survey results that both boiler and heat emitter controls in the UK are generally poor. Computer
simulation of a heating system demonstrated that the use of poorly commissioned boiler controls and the use of thermostatic valves
with limited flow control leads to buildings not maintaining the desired internal temperatures. This results in occupant discomfort
when under-heating occurs and excess fuel consumption when over-heating occurs. Finally, an experimental study demonstrated
that a newly developed boiler control algorithm can offer significant energy savings by controlling the boiler more appropriately and
reducing the effect of poor thermostatic radiator valve use.
Keywords
Heating system , Thermostatic radiator valve , Heating control , Boiler control , Energy efficiency
Journal title
Building and Environment
Serial Year
2005
Journal title
Building and Environment
Record number
408898