Title of article
Estimating airflow rates in air-handling units from actuator control signals
Author/Authors
Huiling Tan، نويسنده , , Richard Thompson and Arthur Dexter، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2006
Pages
8
From page
1291
To page
1298
Abstract
The design and accuracy of simple airflow estimators that are based on actuator control signals are investigated. A computer simulation of the air-circuits of a variable-air-volume air-conditioning system is developed and validated experimentally. The simulation is used to examine the relationship between the supply airflow, the extract airflow and the inlet airflow, and the control signals for the fans and the mixing-box dampers in the air-handling unit (AHU). Based on the simulation results, linear estimators are proposed for the estimation of airflow rates in AHUs. The accuracy of the linear estimators, which are calibrated using measured data collected from the air-conditioning system during testing and balancing, is examined using data collected from a full-scale air-conditioning system. The results show that the estimation errors are less than 8% of full-scale.
Keywords
Airflow smart sensors , Mixing-box , estimators , Air-conditioning
Journal title
Building and Environment
Serial Year
2006
Journal title
Building and Environment
Record number
409174
Link To Document