Application of advanced glazing to high-rise residential buildings in Hong Kong
Author/Authors
Milorad Bojic ، نويسنده , , Francis Yik، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
9
From page
820
To page
828
Abstract
The energy saving that can be achieved by applying advanced glazing to a typical high-rise residential building in Hong Kong was evaluated using the simulation software EnergyPlus. It was found that application of low-e glazing would lead to a reduction in cooling electricity use by up to 4.2%. The saving due to application of low-e reversible glazing would be up to 1.9%; double-clear glazing up to 3.7%; and clear plus low-e glazing up to 6.6%. The achievable saving would depend on orientation of building wings, and type and location of rooms. The analysis suggests that for the high-rise public housing blocks in Hong Kong, the use of expensive advanced glazing would not be economically viable from the point of view of saving in cooling energy cost.
Keywords
Cooling , Low-e glazing , Building envelope