Title of article
Floor-supply displacement ventilation for workshops
Author/Authors
Josephine Lau، نويسنده , , Qingyan Chen، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
13
From page
1718
To page
1730
Abstract
This paper reported the investigation of the performance of floor-supply displacement ventilation with swirl diffusers or perforated panels under a high cooling load (nearly 90 W/m2). The experiment was carried out in a full-scale environmental chamber to obtain reliable data on the floor-supply displacement ventilation for the validation of a computational-fluid-dynamics (CFD) program. Numerical simulations using CFD program were to evaluate the performance of the system for a large workshop. The impacts of several parameters, such as the air change rate, number of diffusers, diffuser location, occupant location, furniture arrangement, partition location, and arrangement of exhausts, on the indoor environment were investigated based on the thermal comfort level and indoor air quality. This study ranked the impacts of these parameters on indoor environment.
Keywords
Computational-fluid-dynamics , Perforated panels , Thermal comfort , Indoor Air Quality , Swirl diffusers , Floor-supply displacement ventilation