• Title of article

    A techno-economic comparison of ground-coupled and air-coupled heat pump system for space cooling

  • Author/Authors

    Hikmet Esen، نويسنده , , Mustafa Inalli، نويسنده , , Mehmet Esen، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    11
  • From page
    1955
  • To page
    1965
  • Abstract
    This paper reports a techno-economic comparison between a ground-coupled heat pump (GCHP) system and an air-coupled heat pump (ACHP) system. The systems connected to a test room in Firat University, Elazig (38.41°N, 39.14°E), Turkey, were designed and constructed for space cooling. The performances of the GCHP and the ACHP system were experimentally determined. The experimental results were obtained from June to September in cooling season of 2004. The average cooling performance coefficients (COPsys) of the GCHP system for horizontal ground heat exchanger (HGHE) in the different trenches, at 1 and 2 m depths, were obtained to be 3.85 and 4.26, respectively and the COPsys of the ACHP system was determined to be 3.17. The test results indicate that system parameters can have an important effect on performance, and that GCHP systems are economically preferable to ACHP systems for the purpose of space cooling.
  • Keywords
    Ground-coupled , Heat pump , Techno-economic analysis , Turkey , Cooling , Air-coupled
  • Journal title
    Building and Environment
  • Serial Year
    2007
  • Journal title
    Building and Environment
  • Record number