Title of article
A techno-economic comparison of ground-coupled and air-coupled heat pump system for space cooling
Author/Authors
Hikmet Esen، نويسنده , , Mustafa Inalli، نويسنده , , Mehmet Esen، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
11
From page
1955
To page
1965
Abstract
This paper reports a techno-economic comparison between a ground-coupled heat pump (GCHP) system and an air-coupled heat pump (ACHP) system. The systems connected to a test room in Firat University, Elazig (38.41°N, 39.14°E), Turkey, were designed and constructed for space cooling. The performances of the GCHP and the ACHP system were experimentally determined. The experimental results were obtained from June to September in cooling season of 2004. The average cooling performance coefficients (COPsys) of the GCHP system for horizontal ground heat exchanger (HGHE) in the different trenches, at 1 and 2 m depths, were obtained to be 3.85 and 4.26, respectively and the COPsys of the ACHP system was determined to be 3.17. The test results indicate that system parameters can have an important effect on performance, and that GCHP systems are economically preferable to ACHP systems for the purpose of space cooling.
Keywords
Ground-coupled , Heat pump , Techno-economic analysis , Turkey , Cooling , Air-coupled
Journal title
Building and Environment
Serial Year
2007
Journal title
Building and Environment
Record number
409456
Link To Document