Applying condensing-temperature control in air-cooled reciprocating water chillers for energy efficiency
Author/Authors
K. T. Chan، نويسنده , , F. W. Yu، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2002
Pages
17
From page
565
To page
581
Abstract
This paper reports on the modelling and findings of the energy performance of an air-cooled reciprocating multiple-chiller plant under the conventional head pressure control and the new condensing-temperature control in a subtropical climate. The simulation model was validated using the operating data of an existing chiller plant. As noted from this existing air-cooled reciprocating chiller plant, there was a substantial efficiency drop at part-load resulting from the head pressure control. If operating at variable lower condensing-temperatures based on the established operating mode of the condenser fans and compressors, it is shown that the chiller consumption can be maintained below 2 kW/refrigeration ton throughout the entire range of outdoor temperature and part-load conditions, giving an average efficiency of 1.08 kW/refrigeration ton. The energy imposition due to cycling on more condenser fans can be compensated by the reduced compressor consumption. Potential energy savings of 18.2 and 29% in the annual chiller consumption are achievable by applying the condensing-temperature control to two existing chiller plants studied. This supports the need to develop the condensing-temperature control as an improvement to the conventional head pressure control.
Keywords
Energy efficiency , Air-cooled chillers , Condensing temperature control , Head pressure control
Journal title
Applied Energy
Serial Year
2002
Journal title
Applied Energy
Record number
414374
Link To Document