• Title of article

    Modeling critical overloading in 6–10/0.4 kV, 250–630 kVA power, oil-immersed transformers

  • Author/Authors

    Gevork Nersessian، نويسنده , , Mark Kaiser، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    10
  • From page
    393
  • To page
    402
  • Abstract
    This study was motivated by its critical importance to the current problem of electricity supplies in Armenia. The time duration for oil-immersed power transformers in both operating (heating process) and standby (cooling process) regimes is determined for a given overloading degree. This process is compared with experimental results on TM-(630,400,250)/10-0.4 kV transformers, and overloading times and cycle durations for each power transformer type are determined. The information may be used to determine the overloading degree of transformers and the permissible duration of their usage in overload regimes.
  • Journal title
    Energy
  • Serial Year
    1997
  • Journal title
    Energy
  • Record number

    415747