• Title of article

    Performance improvement of the combined cycle power plant by intake air cooling using an absorption chiller

  • Author/Authors

    S. Boonnasa، نويسنده , , P. Namprakai، نويسنده , , T. Muangnapoh، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2006
  • Pages
    11
  • From page
    2036
  • To page
    2046
  • Abstract
    This paper studies how to improve the capacity of the combined cycle (CC) power plant which has been operated for 8 years. The most popular way is to lower intake air temperature to around 15 °C (ISO) and 100% RH before entering the air compressor of a gas turbine (GT). Thailand has 3 seasons: winter, summer and rainy season. According to 2003 Bangkok monthly weather data, all year ambient temperature is higher than 15 °C. This research proposes a steam absorption chiller (AC) to cool intake air to the desired temperature level. It could increase the power output of a GT by about 10.6% and the CC power plant by around 6.24% annually. In economic analysis, the payback period will be about 3.81 years, internal rate of return 40%, and net present value 19.44 MUS$.
  • Keywords
    Air cooler , economics , Monthly analysis , Uncertainty , Gas turbine
  • Journal title
    Energy
  • Serial Year
    2006
  • Journal title
    Energy
  • Record number