    Optimal supply air temperature with respect to energy use in a variable air volume system

  • Author/Authors

    Fredrik Engdahl، نويسنده , , Dennis Johansson، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    14
  • From page
    205
  • To page
    218
  • Abstract
    In a variable air volume (VAV) system with 100% outdoor air, the cooling need in the building is satisfied with a certain air flow at a certain supply air temperature. To minimize the system energy use, an optimal supply air temperature can be set dependent on the load, specific fan power (SFP), chiller coefficient of performance, outdoor temperature and the outdoor relative humidity. The theory for an optimal supply air temperature is presented and the heating, ventilation and air-conditioning (HVAC) energy use is calculated depending on supply air temperature control strategy, average U-value of the building envelope and two outdoor climates. The analyses show that controlling the supply air temperature optimally results in a significantly lower HVAC energy use than with a constant supply air temperature. The optimal average U-value of the building envelope is in practise mostly zero.
  • Keywords
    ventilation and air-conditioning , Supply air temperature , Variable air volume system , heating
  • Journal title
    Energy and Buildings
  • Serial Year
    2004