• Title of article

    Empirical validations of solar gain models for a glazing unit with exterior and interior blind assemblies

  • Author/Authors

    Peter G. Loutzenhiser، نويسنده , , HEINRICH, MANZ، نويسنده , , Stephan Carl، نويسنده , , Hans Simmler، نويسنده , , Gregory M. Maxwell، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    11
  • From page
    330
  • To page
    340
  • Abstract
    Experiments performed at the Swiss Federal Laboratories for Materials Testing and Research (EMPA) test cell located in Duebendorf, Switzerland were used for empirical validations of building energy simulation programs. Four solar gain experiments were run with either an exterior Venetian blind or an interior mini-blind mounted over a glazing unit with the blind slats in the horizontal position and with the outer slat edge toward the ground tilted downward 45°. Models of the test cell setup were constructed in two distinctive building energy simulation programs, EnergyPlus and HELIOS, and the measured cooling power in the test cell was compared with the simulated cooling powers. For these experiments, the mean percentage of the absolute mean differences for EnergyPlus and HELIOS were all within 6.1 and 7.1%, respectively.
  • Keywords
    Blind assemblies , Solar gains , Empirical validation
  • Journal title
    Energy and Buildings
  • Serial Year
    2008
  • Journal title
    Energy and Buildings
  • Record number