Title of article
Spinning Reserve from Hotel Load Response
Author/Authors
Brendan Kirby، نويسنده , , John Kueck، نويسنده , , Theo Laughner، نويسنده , , Keith Morris، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
8
From page
59
To page
66
Abstract
Even though preliminary tests were not conducted during times of highest system or hotel loading during the summer, they showed that hotel load can be curtailed by 22 to 37 percent depending on the outdoor temperature and time of day. Full response occurred in 12 to 60 seconds from when the system operatorʹs command to shed load was issued and the load drop was very rapid.
Journal title
The Electricity Journal
Serial Year
2008
Journal title
The Electricity Journal
Record number
433397
Link To Document