• Title of article

    Estimating overpressures in pole-type distribution transformers. II. Prediction tools

  • Author/Authors

    A.، Hamel, نويسنده , , J.-B.، Dastous, نويسنده , , M.، Foata, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    -11
  • From page
    12
  • To page
    0
  • Abstract
    Low-impedance faults are difficult to contain from the point of view of cover retention and tank rupture in poletype distribution transformers. When evaluating a transformerʹs containment capabilities, one needs to consider two aspects: the overpressure caused by an arc of given parameters and the pressure withstand of the tank. This paper presents two methods to calculate overpressures as a function of the arc and all of the relevant geometrical parameters: tank diameter, air-space height, and the depth of the arc below the oil. Both methods have been validated with experiments. Results of tests to determine the pressure withstand of typical tanks are presented. It was found that an average value of the overpressure withstand capability is approximately 100 kPa. For a given tank geometry and fault parameters, a current-limiting fuse would be required if the methods proposed here predict an overpressure of more than 100 kPa.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number