• Title of article

    Fast ferroresonance suppression of coupling capacitor voltage transformers

  • Author/Authors

    M.، Graovac, نويسنده , , R.، ravani, نويسنده , , Wang، Xiaolin نويسنده , , R.D.، McTaggart, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    -157
  • From page
    158
  • To page
    0
  • Abstract
    This paper describes a procedure for fast suppression of the phenomenon of ferroresonance in coupling capacitor voltage transformers (CCVT) without major change in the CCVT design. It is shown that it is possible to adjust parameters of the secondary overvoltage protection and the filter circuit so that the ferroresonance can be cleared in a very short time interval. The study cases reported in this paper show that ferroresonance is effectively cleared within two cycles. An implementation of metal oxide varistors (MOV) as part of passive ferroresonance protection is also addressed. The Electromagnetic Transients Program (EMTP) is used for modeling transients and fine-tuning the ferroresonance suppressing circuit. The studies are conducted on the Trench TEHMP161A CCVT.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    61581