Title of article
Electrical resistance data from fault tests for 2/0 and 4/0 temporary grounding jumpers
Author/Authors
N.، Kolcio, نويسنده , , K.J.، Brown, نويسنده , , W.J.، Page, نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2003
Pages
6
From page
436
To page
441
Abstract
The paper provides ranges of resistance values for 2/0 and 4/0 temporary grounding jumpers (TG jumpers) which when subjected to rated fault tests sustained: (a) no damage, (b) some fusing, and (c) failed by separation. This information is unique and can be used for establishing minimum resistance values for TG jumper testing and selecting pass/fail criterion. The results were obtained from special tests conducted at Bonneville Power Administration and Ontario Hydro Power Technologies high current laboratories.
Keywords
seed yield , sowing date , Nitrogen rate , Rapeseed , Brassica napus
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2003
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
61636
Link To Document