• Title of article

    Transfer function method to diagnose axial displacement and radial deformation of transformer windings

  • Author/Authors

    E.، Rahimpour, نويسنده , , J.، Christian, نويسنده , , K.، Feser, نويسنده , , H.، Mohseni, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    13
  • From page
    493
  • To page
    505
  • Abstract
    Short circuit currents or forces during transport can cause mechanical displacements of transformer windings. The transfer function method is presented as a tool to detect these displacements. In order to be able to evaluate the measurements, the correlation between the characteristics of transfer functions and possible damages must be known. Axial displacement and radial deformation of transformer windings have been studied in this research work using two test transformers. The primary winding of the first transformer for axial displacement has 31 double disk coils (1.3 MVA, 10 kV) and the secondary winding is a four layer winding. The second transformer for the study of radial deformation has 30 double disk coils (1.2 MVA, 10 kV) as primary winding and a one layer winding as secondary winding. The detailed mathematical models were developed for the test objects and a comparison was carried out between measured and calculated results. It is shown that this model can present the behavior of the transformer windings in the frequency domain in the case of sound and displaced conditions.
  • Keywords
    Brassica napus , seed yield , Rapeseed , sowing date , Nitrogen rate
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2003
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    61645