Title of article
Experimental studies on the use of MOV in transformer windings inner protection
Author/Authors
Zhou، Chengke نويسنده , , Yuanfang، Wen نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
6
From page
1441
To page
1446
Abstract
This paper presents experimental investigations into the principle, connection schemes, and the use of a metal oxide varistor (MOV) in transformer winding inner protection. Experiments have been carried out on model transformer and on practical extremely high voltage transformers with standard lightning impulse voltage and oscillatory impulse voltage being applied. Results with and without MOV in parallel with transformer windings from experiments proved the effectiveness of the use of MOV in transformer inner protection.