Title of article
Experimental study of current-dependent grounding resistance of rod electrode
Author/Authors
Ametani، A نويسنده , , S.، Sekioka, نويسنده , , T.، Sonoda, نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
8
From page
1569
To page
1576
Abstract
This paper has experimentally investigated transient behavior of grounding electrode systems especially for a high impulse current up to 40 kA in particular reference with a mutual grounding resistance between the electrodes. The experimental results show that the mutual grounding resistance depends on the applied current similarly to the current dependence of the self-grounding resistance. The phenomenon can be explained by the increase of an effective rod radius and an effective length. The selfgrounding resistance greatly depends on the rod dimension and on the soil resistivity for low currents as analytically well known. However, the parameters cause a less effect on the nonlinear characteristic for high currents exceeding 10 kA.
Keywords
Power-aware
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2005
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
61850
Link To Document