The analysis of ultrasonic signals by partial discharge and noise from the transformer
Author/Authors
Kweon، Dong-Jin نويسنده , , Chin، Sang-Bum نويسنده , , Kwak، Hee-Ro نويسنده , , Kim، Jae-Chul نويسنده , , Song، Kyung-Bin نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
8
From page
1976
To page
1983
Abstract
This paper presents the analysis of ultrasonic signals by the partial discharge in a model transformer as well as by corona in the air at a shielded high-voltage laboratory. In addition, various noises onsite, a 345-kV substation, were measured and analyzed, for example, the vibration by core magnetostriction, cooling pump, cooling fan, onload tap changer (OLTC) operation, OLTC filtering unit operation, and air discharge pulse by corona on the transmission line. Therefore, electrical and mechanical noises onsite were removed using the proper narrow bandpass filter and the noise discrimination algorithm. Also, the developed online ultrasonic detector was applied to detect partial discharge in a 154-kV transformer with a warning level in C/sub 2/H/sub 2/ gas. As a result of an internal inspection, the source of partial discharge was found at the estimated position based on ultrasonic detection and its reliability was verified.